Project/Walls, Doors & Windows

Walls, Doors & Windows

Wall layout with openings · lintels · schedules and quantities · glazing wind pressure · 3D model

Building and walls
Openings: ground storey

Front (z = 0)
Back (z = Lz)
Left (x = 0)
Right (x = Lx)
Openings: typical storeys

Front (z = 0)
Back (z = Lz)
Left (x = 0)
Right (x = Lx)
Lintels and wind
Typical-storey wall load 10.79 kN/m average over the perimeter · ground 13.27 kN/m · 2 doors, 65 windows, 117 m² glazing
Wall dead loads on the perimeter beams (typical storey)
FaceLengthWall htGrossOpeningsNet wallOpening %Line load
Front (z = 0)18.0 m2.70 m48.6 m²10.8 m²37.8 m²22%10.53 kN/m
Back (z = Lz)18.0 m2.70 m48.6 m²10.8 m²37.8 m²22%10.53 kN/m
Left (x = 0)12.0 m2.70 m32.4 m²5.4 m²27.0 m²17%11.19 kN/m
Right (x = Lx)12.0 m2.70 m32.4 m²5.4 m²27.0 m²17%11.19 kN/m

Enter 10.79 kN/m as the cladding line load in the Building designer (it applies the same value on all perimeter beams; clicking the link fills it in for you).

Door and window schedule
MarkDescriptionSizeGroundTypicalTotalArea
D1Door, single timber0.9 × 2.1 m1011.9 m²
D3Door, double glazed leaf pair1.8 × 2.1 m1013.8 m²
W2Window 1.5 × 1.21.5 × 1.2 m111865117.0 m²
Wall quantities (whole building)
Gross wall area672 m²
Openings123 m²
Net wall area549 m²
Wall volume215 mm thick118 m³
Plaster (both faces)1099 m²
Wall weight274 t
Lintels over openingsRC, simply supported, arching masonry load
OpeningClear spanLoad modelw (kN/m)LintelBottom barsBearing
D1 (0.9 × 2.1)0.9 mfull wall height above 2.93215 × 150 mm2Ø120.05 / 4.0 MPaOK
D3 (1.8 × 2.1)1.8 mfull wall height above 2.93215 × 150 mm2Ø120.10 / 4.0 MPaOK
W2 (1.5 × 1.2)1.5 mfull wall height above 2.93215 × 150 mm2Ø120.09 / 4.0 MPaOK

Load: triangular arching load (√3/2 · span high) when the wall above is high enough, otherwise the full wall height. Beams or slabs bearing directly on the lintel must be added as extra line loads.

Glazing and cladding wind pressure at roof level (z = 13.2 m)EN 1991-1-4 simplified
Peak velocity pressure qp(z)0.80 kN/m²
Design suction (zone A, cpi = +0.2)cpe,A = -1.20-1.12 kN/m²
Design pressure (zone D, cpi = −0.3)cpe,D = 0.800.88 kN/m²

Use the larger magnitude to specify glass thickness and fixings with the glazing supplier. Small panels (< 10 m²) can see higher local coefficients than shown.

Scope: rectangular plan, openings evenly spaced along each face, typical storey repeated, wall weights from typical densities, RC lintels simply supported on masonry. Results are an aid only and must be verified by a qualified, licensed engineer before use. National Annex presets are recommended values and must be checked against the official documents.